EVITP - 3B

Horizontales
The voltage drop for a 32a load at 320 feet = 16V with 16,510 cmil wire.
For a Level 2 EVSE at 32 amp is 32a X 1.25 = 40 amp OCPD
Code requires conductor material, length, and operation temperature for calculations.
____ these loads require 1.73 multiplier as if 3 phase load.
Use article 250-122 for 40a circuit with #10AWG CU
____ NECA 413-2012 standard is for EVSE installation and maintenance.
Operating at 6.6kW at 220v provides 30amps supply.
Verticales
____ requirements are found in article 702.
_____ minimum size conductor for 75 degree terminations and 37.5A (30A X 1.25) supply requirements.
___ size needed for 2 percent voltage drop at 400 feet with 208V source at 32 amps.